- Rule out the first three causes above — a worn receptacle is a diagnosis of elimination.
- Test both halves with a lamp you know works. Dead on both, with the breaker on and no GFCI tripped, points here — or to the back-stab cause; in a 1970s–90s home, weigh that one first.
- A separate tell that shows up before total failure: plugs sag or fall out under their own weight. Worn-out contacts are a replace-it sign even while the outlet still works.
buildNo tools schedule15 min
handymanHow to fix it — where your province allows
report Prove it's dead before you touch a screwTurn off the breaker, then verify at the outlet with a non-contact voltage tester — and test BOTH halves, because in many Canadian kitchens older split receptacles are fed by two circuits. No tester, no job. Check the legal note for your province too: in Quebec receptacle replacement is licensed work, and in Ontario it generally needs an ESA notification. If any of this feels like more than you signed up for, it's a fast, inexpensive visit for an electrician.
Replace like-for-like with a CSA-certified tamper-resistant receptacle (the current Canadian Electrical Code standard for homes), wiring under the side screws — never the push-in back-stab holes, even though the new outlet has them. Prove the circuit dead first, and check the legal note for your province before starting.
- Turn off the breaker and prove the outlet dead with a non-contact voltage tester — both halves.
- Photograph the wiring before disconnecting anything, then unscrew the receptacle and pull it straight out of the box.
- Cut back and re-strip any wire that was back-stabbed or shows heat discoloration. Hook each wire clockwise under its side screw — black to brass, white to silver, bare to green — and tighten firmly.
- Tug each wire: it shouldn't budge. Fold the wires back into the box, mount the receptacle, fit the plate.
- Restore power and test both halves with the lamp. Anything that sparks, buzzes, or trips the breaker means stop and call an electrician.
schedule40 min savings$5–25
15 A tamper-resistant (TR) receptacleMatch the amperage marked on the old one (15 A is standard); look for the TR marking and CSA certification Non-contact voltage testerAny CSA-certified tester; check it on an outlet you know is live first, so you know it works
gavel Check your province first AB: permit + inspection required · BC: permit + inspection required · ON: permit + inspection required · PE: permit + inspection required · QC: licensed professionals only
National default shown conservatively as permit-required; the rules are provincial. REVIEW: replace with verified per-province rows before publish.